Load Calculation using Dristeem DriCalc: Humidification Basics Part 7

Randy Kruger and Norm Hall, R.L. Deppmann
 / 
October 17, 2016
Printer Friendly (PDF)

The past couple of blogs used the psychrometric chart and formula to calculate the loads in humidification buildings and processes. This week we look at a valuable shortcut for determining these loads: the Dristeem DriCalc selection program.

Let’s use an example of a humidification load requirement for a school in Flint, Michigan, on an economizer cycle. Let’s assume we have a ducted system with 12,000 CFM of air flow and a requirement in the room of 40% RH at 70°F.

screenshot of the Dristeem DriCalc program - defining system conditions

Next, let’s allow the program to use the location data from ASHRAE. We enter the economizer calculation choice and the 55°F mixed temperature. The program tells us that Flint is at 768 feet above sea level and the design outdoor air temperature is 5.2°F. If the job site was near Flint but on a hill (not many mountains in Michigan!), we could change the elevation.

screenshot of the Dristeem DriCalc program - outside air conditions

Now we choose whether to use the 30-year typical numbers or the 30-year extreme numbers for our load calculation. If this were a museum or process application where the required RH was critical and constantly needed, we would choose the extreme. In the case of buildings, we will use the 30-year typical numbers.

The program calculates the load at a variety of outdoor temperatures and percent of outdoor air. That data is displayed in a table and the design load is the maximum shown in the table.
Our example indicates a need for 89.61 PPH when the outdoor temperature is 40°F and the makeup air is at 50%.

screenshot of the Dristeem DriCalc program - air RH value

The chart shown above would be different if we had chosen the “30-Year Extreme” to calculate the design load rather than the 30-Year Typical. A measure of reasonableness for your client’s first cost is what is applied here. It is rare that the temperatures will be in the extreme range, and it will cause a much larger load and first cost. ASHRAE and Dristeem apply this logic for you to choose or change.

We have a load, we have documentation for our files, and we never looked at a psych chart. Not a bad few Monday Morning Minutes. You can download the Dristeem DriCalc program here.