Domestic Water Recirculation Systems Part 4: High Rise Considerations

RL DeppmannPumps, Plumbing System Design, Domestic Water Recirculation, Balancing, Monday Morning Minutes

The last three articles outlined pump selection in domestic water recirculation systems. In general, these systems have low flow and low head pumps. What happens in a high rise with pressure reducing valves (PRV) in the hot water supply? The pressure reducing valve introduces a fixed pressure drop which must be added to the calculations.

Domestic Water Recirculation Systems Part 3: Pressure Drop

RL DeppmannMonday Morning Minutes, Pumps, Plumbing System Design, Domestic Water Recirculation, Domestic Water Recirculation

The purpose of the domestic water recirculation system is to delivery hot water near a fixture during times when there is no draw. If someone is using hot water in the next room or apartment or process; the hot water is near enough to your fixture so the hot water is delivered in seconds, not minutes.

Parallel Pumping Sketch
Parallel Pumping Sketch

Parallel Pumping: 2-Position Control Valves on Multiple Cooling Towers

RL DeppmannParallel Pumping, Monday Morning Minutes, Commissioning and Balance, Cooling Towers, Pumps, Hydronic System Design, Selection and Specification, Cooling Towers, Piping and Pumps, Parallel Pumping

Over the last few weeks the Monday Morning Minutes posts have looked at pumping issues with multiple condensers and pumps. One of our most-received questions …

Griswold Wafer
Griswold Wafer

Parallel Pumping in Condenser Applications: Limiting the Flow Rate (Part 2)

RL DeppmannPumps, Hydronic System Design, Selection and Specification, Cooling Towers, Piping and Pumps, Parallel Pumping, Parallel Pumping, Monday Morning Minutes, Commissioning and Balance, Cooling Towers

In part 1 of this series we offered an example condenser water pumping system. The design of this example is 800 GPM per condenser for a …