Last week the R. L. Deppmann Monday Morning Minute gave an example of a pump selection for which we applied the margin multipliers to arrive at 24.5 feet of net positive suction head required or NPSHR. Now let’s turn our attention to the cooling tower pump suction piping and net positive suction head available or NPSHA. [Read more…]
It’s all about Pressure – Cooling Tower Pumps and Piping
Last week the R. L. Deppmann Monday Morning Minute left you with a multiplier of 1.3, 1.5, or 2.0 to use with the pump NPSHR. Let’s look at an example this week using the suction energy formula we introduced last week and add one more margin to the formula.
Where Cavitation Begins – Cooling Tower Pumps and Piping
Last week the R. L. Deppmann Monday Morning Minute defined NPSHR, and ended with the Hydraulic Institute (HI) definition as the absolute pressure that will cause the total head of the pump to be reduced by 3%, due to flow blockage from cavitation”. Of importance is the fact that it does not say that NPSHR is where cavitation begins.
It’s All About Terms! – Cooling Tower Pumps and Piping – Part 1
Most cooling tower designs and installations are commissioned without any issues. The few percent of times where problems arise will cause multiple meetings, emails, finger pointing, and added costs. The issues are not caused by bad luck or bad Karma; tower water pumping issues are typically caused by air, dirt, or improper application. [Read more…]