High Rise Considerations The last article, Part 4, showed an example of a high-rise system with pressure reducing valves (PRV’s) and their effect on the …
Domestic Water Recirculation Systems Part 3: Pressure Drop
The purpose of the domestic water recirculation system is to delivery hot water near a fixture during times when there is no draw. If someone is using hot water in the next room or apartment or process; the hot water is near enough to your fixture so the hot water is delivered in seconds, not minutes.
Plumbing Topic: Domestic Water Recirculation Systems Part 2
Let’s assume the domestic hot water supply is a total length of 1000 ft. That is the entire pipe on all of the floors. Let’s also assume an average of 15 BTU/hr/ft of loss through the supply pipe insulation. Now let’s assume the recirc piping is 300 ft total at an average of 10 BTU/hr/ft of loss. What flow rate is required for a 10 degree ΔT? What flow rate is required for a 5 ΔT?
Domestic Water Recirculation Systems Part 1: Flow Rate
The R. L. Deppmann Monday Morning Minutes series will focus on the plumbing portion of the new construction and building facility business for the next few months. The topics will be domestic water recirculating systems, pressure booster systems, volume and instantaneous water heaters, and mixing valves. I’ve had 6 job site visits in the last 2 months to help engineers, service contractors, and facility managers solve problems with domestic water recirculating systems. It seems this is a good place to start.
Variable Speed and ECM Smart Pumps in Domestic Hot Water Recirculation Systems
Domestic hot water supply temperatures and the recirculation system control are receiving a great deal of attention these days. Concerns about legionella growth with low-temperature …





