[Continuation from last week’s MMM] Let’s assume we have a SIX story health care building and the heating system is 90 feet high with a 180 degree supply temperature. The pump and boilers are on the first floor. The BRYAN boilers selected come with 125 PSIG relief valves. Let’s also assume that the pump has a capacity of 800 GPM at 100 feet at design. [Read more…]... READ MORE
Printer Friendly (PDF)
Maximum Pressure of Expansion and Compression Tanks – Part 5
Norm Hall
/
December 12, 2011
Maximum pressure in a hydronic system depends on a number of variables. Last week we used an example to introduce the maximum pressure at the expansion tank. Let’s look at a couple more examples. EXAMPLE TWO: Figure 1 shows a one line diagram of a heating system with a boiler and pumping system. [Read more…]... READ MORE
Printer Friendly (PDF)